Add to Cart
Wireless fire gas detection system Intelligent Fire Alarm Control Panel for Block /Home/School Safety(64 point location)
Preface
The JB-TB-TC5126W wireless intelligent fire alarm control panel is a new generation of intelligent integrated wireless fire alarm control panel designed and developed under our company's full investigation of the fire protection market demand, summarizing the company's fire engineering experience in the fire protection industry for many years, and fully meeting the requirements of GB4717-2005 fire alarm control panel, GA1151-2014 General Requirements for Wireless Communication Function of Fire Alarm System and GB16806-2006 Fire linkage Control System.
The control panel adopts wall-mounted structure and modular design, and has the specifications of full function, high reliability and flexible configuration. The system adopts color LCD display, which is easy to operate, easy to learn and use. This control panel can be connected with alarm points by wireless way. JB-TB-TC5126W wireless intelligent fire alarm control panel can be matched with point-type wireless heat detectors, wireless smEntere detectors, MCP, wireless combustible gas detectors, etc. produced by our company as required to meet various needs of fire engineering. Please read this manual carefully before using and operating this control panel. After commissioning and acceptance, this manual should be taken care of by a special person and properly kept for future reference!
Introduction of control panel components
In order to make you more familiar with the control panel, the following briefly introduces the main components of the control panel:
·Main control module
The main control board is responsible for analyzing and processing the information data transmitted by other components in the system, and according to the data analysis results, commanding other components in the system to execute corresponding commands, such as control speaker voice alarm, etc.
·Display module
The display component provides the main output interface of alarm information, as well as the daily maintenance and query interface.
·Key module
Matrix buttons are used in the control panel, which is very convenient for users to set up and maintain the system.
·Power module
The power supply module supplies power for the whole system equipment, and provides power fault signals such as main power fault, standby power fault and standby power undervoltage, and has good anti-interference ability.
·Wireless 470 module
The 470MHzFSK coded bidirectional communication can communicate with 32 wireless devices.
·Loop control panel
This control panel can be connected with 18 intelligent loop control panels, which has less wiring and high reliability. Each start/stop key on the manual fire control startup panel can be associated with any bus equipment connected to the system by definition, and complete the start/stop control of the bus linkage equipment, thus thoroughly solving the inherent problems of engineering wiring, equipment configuration and installation and debugging of the alarm linkage integrated system.
·Direct control panel
This control panel can be equipped with 6-way three-wire direct control panel, and has the functions of detecting open circuit and short circuit of output line, which can guarantee the reliability of the control module itself and its connection with important equipment to the maximum extent.
Main technical specifications
1 power supply
Main power supply: AC 220V (3.5A) voltage range+10% ~-15%.
Backup power supply: lead-acid battery 12V/3.3Ah 2 batteries.
2 Operating environment
Temperature: -10℃ ~+55℃.
Humidity: ≤95%, non-condensing.
3 Equipment capacity
Number of loops: two wireless loops.
Number of components in each loop: 32 points.
Number of network segments: 29.
4 wire system requirements
CAN bus: RVS twisted pair with cross-sectional area ≥ 1.0mm.
5 Radio frequency parameters
Transmit power: < 20dBm
Communication distance: ≤50m
Frequency band: 470MHz
6 Implementation standards
Executive standard: GB4717-2005 fire alarm control panel
GA 1151-2014 general requirements for wireless communication function of fire alarm system
GB16806-2006 fire linkage control system
Fault and Abnormal information processing and Regular Check
No. | Fault | Reason | Solution |
1 | No display or abnormal display after starting up | A. The power supply is abnormal B. Poor connection with the display panel cable | A. Check the 24V power supply B. Check the connecting cable
|
2 | "main power failure" after starting up | A. No AC power B. The AC fuse is burnt out | A. Check and connect the AC wire B. Replace AC fuse (see label for parameters) |
3 | after starting up, "standby failure" is displayed. | A. The insurance is broken B. Poor line connection C. Loss or damage of battery | A. Change the safety tube (see label for parameters) B. Open the power box and check the relevant connectors C. after starting up for more than 8 hours under AC power supply, replace the battery if the fault cannot be eliminated. |
4 | can not register the external display panel | communication line connection error or bad | Check the power line and communication line of the fire display panel
|
5 | do not print | A. Not set to print on B. Bad connection of printer cable C. The printer is broken. | A. Reset the settings B. Check and connect well C. Change the printer |
6 | no respond after pressing the manual button | A. Manual prohibition status B. Bad cable connection of manual fire startup disk | A. Reset startup mode B. Check and connect well |
7 | equipment failures | A.Equipment disconnection B. The equipment is damaged | A. Check the connection B. Replacement of equipment
|
8 | clock fault, storage fault, loop fault, etc. | A. Environmental interference B. Aging of corresponding parts | A. Check whether the grounding is in good condition B. inform our technical service department |
Company Profile
Henan Weiguo Intelligent Technology Co., LTD., founded in 2015, is an important subsidiary of Hanwei Electronics Group Corporation (Stock no.:300007) in the field of intelligent healthy, safe home and IoT business. Henan Weiguo Intelligent Technology Co., LTD., relying on the core sensor technology, focuses on gas and smoke alarm, air quality monitor, alcohol tester and firefighting products. Based on introduction of featured technology from both Hanwei Electronics Group Corporation and abroad, Henan Weiguo intelligent Technology Co., LTD., has developed into an innovative company with the collection of design, R&D development, production, sales and service. We will always be committed to becoming the leader in intelligent hardware, providing safe, healthy, environmentally friendly and intelligent working and living environment for families and users all over the world.
FAQ
Q1: Are you manufacturer?
A: (yes)
Q2: What is the lead time?
A: usually
Fire control: one week working day
bulk quality: three weeks working days
Emergency lights: two weeks working days
bulk quality: four weeks
Q3: How do you ship the goods and how long does it take arrive?
A: We usually ship by DHL, UPS, FedEx or by Air. 3-5 days after payment received.
Q4: Can I have a sample order?
A:Yes,we welcome sample order to test and check quality.
Q5: Do you offer OEM service?